Interested
in the EPGK-F ?
General Information:
EPGK-F is designed to test the mechanical dynamic characteristics of vacuum, SF6, with oil and etc high voltage and low voltage circuit breakers.

Features:
  • ♦ Auto identify open or close status. To give correspondent close or open prompt according to channel’s status.
  • ♦ Can detect and prompt connection status of 6 channels (12 channels is for option), it’s convenient to detect connection.
  • ♦ 100 groups data storage.
  • ♦ Large LCD 320×240, can read clearly even in direct sunlight.
  • ♦ Friendly English interface, easy to operate.
  • ♦ Graphical analysis function, to realize waveform and measuring processed data to displayed at same screen.
  • ♦ Delay protection, auto switch off coil voltage after breaker acting, to protect breaker and HV tester.
  • ♦ Open-closed test by auto or manual is selectable.
  • ♦ High/low voltage test is all available. Auto seeking the lowest opened or closed voltage.
  • ♦ Re-closed testing, could test closed-open, open-close, open-close-open and etc parameters.
  • ♦ Build-in thermal printer.

Specification:
Specifications
Time test:
6 channels (12 channels is for option)
Open(Close)time
Open(Close)one phase no- synchronism
Open(Close)phase to phase no-synchronism
Close(Open)bounce time(bounce numbers)
Test range:0.01ms~10000ms
Accuracy:1ms~100ms: 0.5%±2digits
>100ms: 1%±2digits
Velocity test:
Open(Close)velocity
Pointed periods of time(travel period or angle period)average speed Open(Close)max. speed.
Range: 1mm Sensor:0.01~25.00m/s,
0.1mm sensor: 0.001~2.50m/s
0.5°angle sensor: 0.01~25.00m/s
Universal sensor: 0.01~25.00m/s
Travel test: Active contactor travel
Contactor travel (open distance)
Overshoot travel or bounce travel (over travel)
Sensor measuring range:
Linear position sensor 50mm, Resolution: 0.1mm, travel 0.1~50mm.
Linear position sensor 300mm, Resolution: 0.1mm, travel 10~300mm
Linear position sensor 500mm, Resolution: 1mm, travel 10~500mm
360 sensor:360о,resolution:0.5о ,travel 5mm~999mm.
Universal sensor: resolution: 0.1mm, travel 5mm~999mm.
Current measuring: The displayed current is max. open(close) coil current value.
AC source: AC 220V ± 20%;50Hz ± 2% (Can be customized)
DC source: Output voltage:15~265V continuous adjustment,output current:≤ 15A(short time)
Control unit oversize: 360×250×140mm
Working temperature: -20℃~+50℃
RH: ≤90%