General Information:EPCP-III is portable analyzer designed for analyzing current transformers and voltage transformers of protection or measurement use, which is suitable for laboratory and on-site test.
Features: - ♦ 5.7’ LCD screen, display clearly even under sunshine.
- ♦ Rotating photoelectric mouse, easy to operate.
- ♦ Build in printer to print test result automatically after testing completed.
- ♦ Full functions, satisfy all kinds of CT (protection CT, measuring CT, TP) test requirements, such as excitation characteristic test, turn ratio, polarity, secondary winding resistance, secondary burden, ratio error, angular difference etc. Also, it can be used to test excitation characteristic, turn ratio, polarity, secondary winding resistance, ratio error, angular difference etc. all kinds of PT.
- ♦ Auto test CT/PT parameters on knee point voltage/current, 5% and 10% deviation curve measurement, Accuracy limit factor (ALF), safety factor (FS), second time constants (Ts), residual magnetism factor (Kr), saturated and unsaturated inductance.
- ♦ Accurately measure ratio error and angular error. Max. Ratio error ±0.1% is permitted. Max. Angular error ±5min if permitted. It can measure 0.2S class CT and turns ratio range is 1-40000.
- ♦ Complied with IEC60044-1, IEC60044-6 standards of all kinds of CT/PT.
- ♦ Using variable frequency method can deal with60kV CT test when keen point is as high as 60kV.
- ♦ Easy to use. To test CT DC resistance, excitation and polarity only by one button. All CT tests adopt same one connects method except load test.
- ♦ To export test data by U disk.
- ♦ 1000 groups’ data storage, data can be saved even power failure.
- ♦ Friendly interface, English graphical interface.
- ♦ Small size and portable, weight less than 10KG.
Main Test Functions: Model | EPCP-III |
Test Item | CT: Excitation characteristic, Turns Ratio, Polarity, Secondary Winding Resistance, secondary load, Ratio test and angular tests. PT:Excitation characteristic, Turns Ratio, Polarity、Secondary Winding Resistance. |
Power Supply | Input Voltage | 185Vac~250Vac |
Allowed Input Voltage | 85Vac~264Vac |
Frequency | 50/60Hz |
Allowed Frequency | 45Hz~65Hz |
Input Power | 800VA |
Connector | Standard AC socket 60320 |
CT Turns Ratio Accuracy | Turns Ratio 1~2000 | 0.05% (Typical value)/0.1% (Guarantee value) |
Turns Ratio 2000~5000 | 0.07% (Typical value)/0.2% (Guarantee value) |
Turns Ratio 5000~40000 | 0.1% (Typical value)/0.5% (Guarantee value) |
PT Turns Ratio Accuracy | Turns Ratio 1~2000 | 0.05% (Typical value)/0.1% (Guarantee value) |
Turns Ratio 2000~5000 | 0.07% (Typical value)/0.2% (Guarantee value) |
Turns Ratio 5000~40000 | 0.1% (Typical value)/0.5% (Guarantee value) |
Phase Measurement | Resolution | 0.01min |
Accuracy | 2min (Typical value)/5min (Guarantee value) |
Secondary Winding Resistance | Range | 0Ω~300Ω |
Resolution | 1mΩ |
Accuracy | 0.1% (Typical value)/0.2%±2mΩ (Guarantee value) |
AC Load Measurement | Range | 0VA~1000VA |
Resolution | 0.01VA |
Accuracy | 0.1% (Typical value)/0.2%±0.02VA (Guarantee value) |
Output | Voltage | 0Vac~180Vac |
Current | 0Aeff~12Aeff(36Apeak) |
Power | 0VAeff~800VAeff(1800VApeak) |
Working Condition | Operation Temperature | -10℃~+50℃ |
Storage Temperature | -25℃~+70℃ |
Relative Humidity | 5%~95%,No Condensation |
Dimension | 360×285×145mm3 |
Weight | 8kg (Excluding accessories) |