EPRP-605Relay Protection Tester Main Features: ♦ Flexible combination of voltage and current outputSix phase voltage and six phase current can be output, which has made it is possible to be any combition, such as the output mode of the combination of conventional four phase current and three-phase current, six phase voltage mode, six phase current mode and 12 phase output mode. It not only can be compatible with the traditional way of various tests, but also can conveniently carry out differential test of three-phase transformer.
♦ Operation modeThe device is directly connected with a computer or a desktop computer, which is convenient and efficient and stable performance.
♦ A new hi-fi linear power amplifier The output port has always insisted on using the modular linear power amplifier instead of the switching power amplifier, which has the high fidelity and high reliability function and excellent performance. High-mid frequency will not be produced to disturb the test, also ensure the smoothing accuracy of waveform produced by the whole course of the high current to the tiny current is excellent.
♦ High performance MainframeThe output part adopts DSP control, which has fast operation, real-time digital signal processing capability, wide bandwidth and high-resolution D/A conversion control. The output waveform has the features of high precision, small distortion and good linearity. With using many advanced technology and precision components and materials and the structure of professional design, the device has the features of small volume, light weight, full function, easy to carry, boot can work, flow test is very convenient.
♦ Powerful software functionIt can complete all kinds of high automatic validation work which is large and complex. It can also conveniently test and scan protection setting, playback of fault, real-time store test data, display vector, online print report and so on. Besides, six-phase current can facilitate the test of three-phase differential protection.
♦ Independent DC power outputAn 110V and 220V adjustable DC power is designed to supply output.
♦ Complete interfaceThe device with USB communication port can communicate with the computer and other external devices.
♦ Perfect self-protection functionWith reasonable design of the heat dissipation structure and the reliable and perfect hardware protection measures, it has the power soft start function and the software of the fault self-diagnosis and the output latch function.
Nominal Parameter: Current channel number | Standard six phase |
Voltage channel number | Standard six phase |
AC current output range | 30A / phase or 180A (six phase parallel) |
DC current output range | 10A DC /phase |
AC voltage output range | 120V AC /phase |
DC voltage output range | 160V DC / phase |
♦ AC current output The each phase output when six phase current output (RMS): | 0~30A output precision 0.1 grade |
The each phase output when three phase current output (RMS): | 0~60A |
The six phase parallel current output(RMS): | 0~180A |
The allowed working value when the phase current work long time (RMS): | 10A |
The maximum output power of phase current | 450VA |
The maximum output power when six phase parallel current output | 1000VA |
The allowed working time when six phase parallel current maximum output | 10s |
Frequency range(fundamental wave) | 0~1000Hz |
Harmonic order | 0~20 |
♦ DC current output Current output | 0~±10A / phase output precision 0.2 grade |
The maximum load voltage output | 20V |
♦ AC voltage output Phase voltage output RMS value: | 0~120V output precision 0.1 grade |
Line voltage output RMS value: | 0~240V |
The output power of phase voltage/ line voltage: | 80VA / 100VA |
Frequency range(fundamental wave): | 0~1000Hz |
Harmonic orders: | 0~20 |
♦ DC voltage output The output amplitude of phase voltage: | 0~±160V output precision 0.2 grade |
The output amplitude of line voltage: | 0~±320V |
The output power of phase voltage/ line voltage: | 70VA / 140VA |
♦ Input and output On-off input | 8 channels |
Idle contact | 1~20mA,24V |
Electric potential contacts | “0”:0 ~ +6V; “1”:+11 V ~ +250 V |
4 channels output | DC:220 V/0.2 A;AC:220 V/0.5 A |
♦ Time measurement range0.1ms ~ 9999s, measurement accuracy <0.1ms