Interested
in the EPBTC ?
General Information:

EPBTC Transformer Load / No-load Tester is a high-precision instrument used for measuring characteristic parameters such as transformer capacity, no-load, load, and energy efficiency level. EPBTC is a multifunctional measuring instrument, equivalent to the usual two testing instruments: transformer capacity tester and transformer characteristic parameter tester. It can accurately measure a series of power frequency parameters such as capacity, energy efficiency level, type, no-load current, no-load loss, short-circuit (load) loss, impedance voltage, etc. of various transformers. (Also called Transformer Power Analyzer)

Also called: Transformer Iron & Copper Loss Tester, Transformer load/no-load Tester, Transformer Capacitance and Load No Load Tester


Standard: IEC270

Features
1. It can accurately measure the capacity of various distribution transformers, which is convenient and accurate.
2. It can measure the no-load current, no-load loss, short-circuit voltage and short-circuit (load) loss of the transformer.
3. The tester automatically switches the range within the instrument, allowing the measurement voltage and current range to be wide and the wiring to be simple..
4. When doing the no-load and load test of the three-phase transformer, the instrument can automatically judge whether the wiring is correct, and display a vector diagram of the three-phase voltage and current.
5. One can measure the load test below 1000kVA distribution transformer at full current, measuring the load test in 1/3 rated current can be completed under 3150kVA distribution transformers (in the 1/3 of the rated current under the tester can be converted to the load loss parameters under the rated current).
6. All test results are automatically corrected. The tester can carry out many kinds of correction, such as waveform correction, temperature correction, non-rated voltage correction, non-rated current correction and so on.
7. 320 * 240 large screen, high brightness LCD display, touch button makes the operation more convenient, wide temperature LCD with brightness adjustment, can adapt to the winter and summer season.
8. The tester can be preset by the user 40 sets of sample parameters, and these parameters can be deleted at any time as required, and the use is very convenient.
9. With real-time electronic clock, automatically record the date and time of the test, which is conducive to the preservation and management of the test results.
10. Panel type thermal printer, can quickly print the results of the field test.
11. Data (test set, measurement results, test time, etc.) with the power down storage and browsing capabilities, can store 500 sets of test results, and the computer can send data online.
12. Allow external voltage transformer and current transformer to expand the range measurement, can measure any parameters of the subject matter.

Technical Specifications:
Test Items RMS of three phase voltage: Uab, Ubc, Uca.
Average value of three phase AC voltage: Uab, Ubc, Uca.
RMS of three phase current: Ia, Ib, Ic.
Percentage of No-load loss and No-load current: Po, Io%.
Load loss, impedance voltage percentage, short circuit impedance: Pt, ekt, Zt.
Load loss, impedance voltage percentage and short circuit impedance at any specified temperature.
Transformer actual capacity and judged capacity.
External power supply: 220VAC±10%, 45Hz~55Hz
AC voltage Range 10~650V
Resolving power 0.001V
Accuracy 0.2%±0.001V
AC Current Range 0.5~100A
Resolving power 0.001A
Accuracy 0.2%±0.001A
Frequency Range 45Hz~65Hz
Resolving power 0.001Hz
Accuracy 0.2%±0.001Hz
Power Range 0~39kW
Resolving power 0.001kW
Accuracy <±0.5%(CosΦ>0.1), ±1.0%(0.02
Environment condition Operating temperature -10ºC~+50ºC
Storage temperature -25ºC~+70ºC
Humidity 5%~95%, No condensation
Size 400×300×220mm
Weight ≈8kg (Excluding test wires)

Measurement range
Capacity 10kV Oil-immersed, dry type transformer: 30kVA ~ 2500kVA
35kV Oil-immersed transformer: 50kVA ~ 31500kVA
20kV Dry type transformer: 50kVA ~ 2500kVA
35kV Dry type transformer: 50kVA~2000kVA
Voltage 0 ~ 450V (phase voltage),
0 ~ 800V (line voltage), auto switching range
Current 0 ~ 100A, auto switching range
Frequency 45Hz~65Hz

Test accuracy
Voltage 20~100V, ±0.2%FS, 100~450V, ±(0.2%+3 digit)
Current 0.5~10A, ±0.2%FS, 10~100A, ±(0.2%+3 digit)
Power ±0.5% (CosΦ>0.1), ±1.0% (0.02